Condition Desc. used-near new
Manufacturer Square D
Volts 4160
Model 5GSB2-350-1200
Amperes 1200
Weight 1050

This is a truck freight item which will require us to get a shipping quote. You can complete the checkout and provide payment information but you will not be charged until you agree to the freight charges. We will contact you with the freight quote. If you are providing your own shipping contact us.

Breaker Square D 5GSB2-350-1200 for GE Magne-blast AM4.16-350-1200

Mfg: Square D

Mdl: 5GSB2-350-1200

$12,500.00

Quantity: 11

Inventory #: 8759

Call 610-286-1655 with questions or shipping quotes.
REQUEST MORE INFO

Barely used Square D brand vacuum breaker that was designed to be drop-in replacement for the GE Magne-Blast AM-4.16 switchgear system.  The breaker is a Square D Magnum medium voltage KVR unit that was retrofitted to fit into the GE Magneblast switchgear system.  Units were only operated 150-300 times and looks nearly new.  

  • Medium Voltage Direct Replacement 
  • Square D Magnum that is retrofitted to fit into a GE Magne-blast system
  • 1200 amps
  • 4160V
  • 150-300 operations on meters

Top label:

  • Type: 5GSB2-350-1200
  • s/n: 27787074-003H
  • style: AM4.16-350-1200
  • rated max voltage freq: 4.76 kV/60 Hz
  • rate voltage range factor, K: 1.00
  • rated dielectric strength: 19 kV/60 kv   BIL
  • rated cont. current: 1200 amp
  • rated SC current: 50kA
  • rate interrupting time: 5 cycles
  • control voltage range charge: 85 - 140 VDC
  • trip: 65-140 VDC
  • close: 85-140 VDC

Side label:

  • Type: KVR
  • factory order number: 28872903-001
  • Catalog no: V5FK1233V00
  • mfg date: 1/12
  • rate max voltage: 4.76 kV
  • voltage range factor: 1.00
  • impulse withstand(bil): 60kV
  • 50/60 hz
  • continuous current: 1200
  • short circuit current: 50kA sym
  • MVA class reference: 350mva
  • interrupting time: 5 cycles
  • circuit breaker weight: 360
  • instruction bool no: 6055-56
  • closing coil voltage range: 100-140 VDC
  • tripping coil voltage range: 70-140 VDC