Condition Desc. used-near new
Manufacturer Square D
Volts 4160
Model 5GSB2-350-2000
Amperes 2000
Serial # 27787074-002G
Weight 1110

This is a truck freight item which will require us to get a shipping quote. You can complete the checkout and provide payment information but you will not be charged until you agree to the freight charges. We will contact you with the freight quote. If you are providing your own shipping contact us.

Breaker Square D 5GSB2-350-2000 for GE Magne-blast AM4.16-350-2000

Mfg: Square D

Mdl: 5GSB2-350-2000

$12,500.00

Quantity: 3

Inventory #: 8758

Call 610-286-1655 with questions or shipping quotes.
REQUEST MORE INFO

Barely used Square D brand vacuum breaker that was designed to be drop-in replacement for the GE Magne-Blast AM-4.16 switchgear system.  The breaker is a Square D Magnum medium voltage KVR unit that was retrofitted to fit into the GE Magne-blast switchgear system.  Units were only operated 150-300 times and look nearly new.  

  • Medium Voltage Direct Replacement 
  • Square D Magnum that is retrofitted to fit into a GE Magne-blast system
  • 2000 amps
  • 4160V
  • 150-300 operations on meters


Top label:

  • Type: 5GSB2-350-2000
  • s/n: 27787074-002G
  • style: AM4.16-350-2000
  • rated max voltage freq: 4.76 kV/60 Hz
  • rate voltage range factor, K: 1.00
  • rated dielectric strength: 19 kV/60 kv   BIL
  • rated cont. current: 2000 amp
  • rated SC current: 50kA
  • rate interupting time: 5 cycles
  • control voltage range charge: 85 - 140 VDC
  • trip: 65-140 VDC
  • close: 85-140 VDC

Side label

  • Type: KVR
  • factory order number: 17-29363333-001
  • Catalog no: V5FK4233Y00
  • mfg date: 12/11
  • rate max voltage: 4.76 kV
  • voltage range factor: 1.00
  • impulse withstand(bil): 60kV
  • 50/60 hz
  • continuous current: 2000
  • short circuit current: 50kA sym
  • MVA class referance: 350mva
  • interupting time: 5 cycles
  • circuit breaker weight: 360
  • instruction bool no: 6055-56
  • closing coil voltage range: 100-140 VDC
  • tripping coil voltage range: 70-140 VDC